Optimasi Gangguan Surja Petir Dengan Pengaturan Jarak Lightning Arrester

Nurmiati Pasra, Samsurizal Samsurizal, Kartika Tresya

Abstract


Several cities in the Indonesian region are tropical areas that have a fairly high level of lightning insecurity, one of which is the Jayapura city. Demographic conditions make up to the occurrence of lightning strikes and fall into the category of regions that have a fairly high level of lightning insecurity. One of the causes of frequent interference in high-voltage systems comes from lightning. For this reason, it is necessary to optimize the interference that may occur by setting the distance between the lightning arrester and the transformer so as to minimize the level of interference that can occur due to lightning. Lightning arrester is one of the protection tools used to protect equipment against short circuit and lightning. From the results and analysis that has been done obtained results with a distance of 4.11 m and 4.40m which has an impulse voltage value due to surja that arrives at its transformer at skyline substation of 114.22 kV and 114.80 kV.  While the optimal distance from the placement of the lightning arrester with the transformer is at a distance of 0.58m at that distance obtained a large value of impulse voltage due to surja that arrives at the transformer of 107.16 kV. The value of impulse voltage due to surja is smaller when compared to the value of impulse voltage due to surja obtained from the lightning arrester separated from the transformer. So that in this study it can be concluded that a good lightning arrester placement is required to be as close as possible to the equipment it protects in order to neutralize the disturbances that can occur.


Keywords


Lightning Arrester, Distance Optimization, Protection

Full Text:

PDF (Indonesian)

References


Marsudi, D. (2005). Pembangkitan Energi Listrik. Jakarta: Penerbit Erlangga.

Pedoman Pemulihan Sistem Tenaga Listrik Jawa-Bali . (2007). Depok: PT PLN (Persero) P3B Jawa-Bali Bidang Operasi Sistem.

Shahidehpour, M., & Eremia, M. (2013). Handbook of Electrical Power System Dynamics. Piscataway: IEEE Pres Editorial Board

Fitrianto, A. (2005). Evaluasi Blackstart PLTU Suralaya. Jakarta: UniversitasIndonesia.

Fausta, A., Untoro, A., & Samsurizal, S. (2020). Analisis Pengaruh Keandalan Transformator Arus (Current Transformer) Terhadap Rugi Energi Pelanggan TR 3 Phase Di PT. PLN (Persero) UP3 Cikokol (Skripsi, Institut Teknologi PLN).

Kadir, A. (2006). Distribusi dan utilitas tenaga listrik. Jakarta: UniversitasIndonesia.

Marsudi, D. (1990). Operasi Sistem Tenaga Listrik. Jakarta: Balai Penerbit & Humas ISTN.

Stevenson, W. (1984). Analisa Sistem Tenaga Listrik (Edisi Keempat). Jakarta: Erlangga

Hajar, I. (2017). Kajian Pemasangan Lightning Arrester Pada Sisi HV Transformator Daya Unit Satu Gardu Induk Teluk Betung. Energi & Kelistrikan, 9(2), 168–179.

Jayanthana. (2020). Analisia Penempatan Lightning Arrester Pada Cable Head 60 Sebagai Pengaman Transformator Gis Bandara Ngurah Rai. Jurnal Spektrum, 7(1), 144–151.

Marikena, N., Sumarlin, & Aritonang, R. P. (2017). Jurnal Ilmiah “DUNIA ILMU” Vol. 3. No. 1 Juli 2017. Jurnal Ilmiah Dunia Ilmu, 3(1).

Nurhaidi, R., & Rajagukguk, M. (2015). Penentuan Letak Optimum Arrester Pada Gardu Induk (GI) 150 kV Siantan Menggunakan Metode Optimasi. 1–8.

PLN. (2014). Buku Pedoman Pemilihan Arrester untuk Jaringan Transmisi 66 kV, 150 kV, 275 kV, dan 500 kV. PT. PLN (Persero).

Putra, I. J. D. P. (2019). Analisis Pemeliharaan Dan Penempatan Lightning Arrester Bay Bawen 2 Gardu Induk 150.

R, B. A., Patras, L. S., Lisi, F., Elektro, T., Sam, U., Manado, R., & Manado, J. K. B. (2018). Analisa Koordinasi Isolasi Peralatan di Gardu Induk Teling 70 kV. Jurnal Teknik Elektro Dan Komputer, 7(2), 10.

Samsurizal, S., & Hadinoto, B. (2020). Studi Analisis Dampak Overload Transformator Terhadap Kualitas Daya Di PT. PLN (Persero) UP3 Pondok Gede. KILAT, 9(1), 136-142.

Sari, K (2019). Simulasi Jarak Arrester Sebagai Proteksi Transformator Menggunakan Software ATP (Alternative Transients Program) Pada Gardu Induk Seduduk Putih. Universitas Sriwijaya

Samsurizal, S., & Nugroho, T. G. (2020). Studi Perhitungan Rele Tanah (GFR) Akibat Gangguan Simpatetik Trip Pada Penyulang Tegangan Menengah. JURNAL ILMIAH SUTET, 10(1), 1-14.

T, S. H. S., Prastyono, I., & Pambudi, E. (2018). Evaluasi Sistem Penempatan Lightning Arester Pada Transformator Gardu Induk 150 kV

Pedan. Ependi, Evaluasi Sistem Penempatan Lightning Arester Pada Transformator Gardu Induk 150. 5(2), 47–53




DOI: http://dx.doi.org/10.36055/setrum.v11i1.14514

Refbacks

  • There are currently no refbacks.